Question
Download Solution PDFA Y-Δ transformer bank CANNOT be paralleled with either a Y-Y or a Δ-Δ transformer bank because the phasor voltage difference between the two systems would be:
Answer (Detailed Solution Below)
Detailed Solution
Download Solution PDFThree phase transformer connection
A Y-Δ (Wye-Delta) transformer introduces a 30-degree phase shift between the primary (Y-side) and secondary (Δ-side) voltages.
This means that if a Y-Δ transformer is connected in parallel with a Y-Y or Δ-Δ transformer (which do not introduce this phase shift), there will be a phase difference of 30° between the secondary voltages.
The resulting phasor voltage difference between the two transformer systems is given by:
\(V_{diff}=V_{secondary} \times sin(30)\)
\(V_{diff}=V_{secondary} \times 0.5\)
Thus, a Y-Δ transformer bank cannot be paralleled with a Y-Y or Δ-Δ bank because of this voltage difference, which would cause circulating currents and instability.